Operational specification
Measuring range***:
VDC Digitizer: 0 – 30VDC
Precision VDC Digitizer: 0 – 30VDC
Resolution:
VDC Digitizer: 0.1V
Precision VDC Digitizer: 0.01V
Accuracy:
VDC Digitizer: +/- 120mV
Precision VDC Digitizer:
In range: 0-10V: +/- 40 mV
In range: 10-30V: +/- 120 mV
Input Impedance:
100kΩ
Measuring Frequency*:
Every 10 sec
Report Frequency*:
Reports every 2 min. Or immediately if trigger for critical data transmission is reached, see below
Trigger for Critical Data Transmission*:
VDC Digitizer: 2V
Precision VDC Digitizer: 200mV
Operating Environment:
Ambient temperature: -40 – 85 °C
Relative humidity: 0-100%
Altitude: < 2000m above sea level
Pollution degree: 4
IP Grade:
IP 67, wet conditions, indoor use
Radio Frequency:
863-870 MHz / 902-928 MHz
Battery Type:
Li-SOCl2, 3.6V
Expected Operating Time**:
Up to 10 years
* Adjustable on request
** Depends on measurement frequency, amount of critical data transmissions and ambient temperature
*** Voltage outside the range 0-30VDC may permanently damage the device
Physical specification
Materials:
POLYblend 65 FS / TPU
Connection:
2 x 40 cm RADOX 155 0.25 mm2
Dimensions LxWxH:
37x23x14mm
Regulatory
Certifications:
CE marking
UK CA
FCC
Industry Canada
Directives/Standard:
IEC 61010-1:2010
FCC Part 15C
RED 2014/53/EU Radio
Equipment Regulations 2017